Motor Nameplate Data
Motor Electrical Results
Full Load Amps (FLA)
A
NEC Wire Ampacity
A (FLA × 1.25)
NEC Breaker Size
A (FLA × 2.5)
Input kW
kW
NEC 310 Wire Sizing (THHN/THWN 75°C, Conduit)
AWG/MCMAmpacityAdequate for FLA × 1.25?
NEC 430.22: Branch-circuit conductors must be rated at least 125% of motor FLA. NEC 430.52: Inverse-time breaker sized at 250% of FLA (round up to next standard size). Always verify with AHJ and local code amendments. Breaker standard sizes: 15,20,25,30,35,40,45,50,60,70,80,90,100,110,125,150,175,200,225,250,300,350,400,450,500A.
Free 14-Day Trial  ·  No Credit Card

Do the full calculation in AIM Works

This calculator handles one step. AIM Works runs the complete MEP design workflow — thermal load calculations, duct & pipe networks, equipment selection, code compliance, and an AI design assistant — in one tool.

  • ✓  ASHRAE 62.1 ventilation + CLTD/CLF/RTS load methods
  • ✓  Darcy-Weisbach pipe & duct network solvers
  • ✓  ASHRAE 90.1 / IMC / NFPA compliance checks
  • ✓  20 free AI design messages included in trial
Try It Free for 14 Days →
No credit card  ·  Cancel anytime
See plans & pricing →