Air Changes per Hour (ACH)

Convert between air changes per hour, airflow, and room volume.

Solve For
ACH
—
air changes/hr
Minutes per Change
—
min / change
Typical Target
—
—
ACH Reference — Typical Targets and Their Basis
Space TypeTypical TargetBasis
Office4–6 ACH total supplyRule of thumb. ASHRAE 62.1 OA ≈ 0.6 ACH*
Conference Room6–10 ACH total supplyRule of thumb. ASHRAE 62.1 OA ≈ 2.1 ACH*
Classroom (age 9+)6–8 ACH total supplyRule of thumb. ASHRAE 62.1 OA ≈ 3.1 ACH*
Corridor2–4 ACH total supplyRule of thumb. ASHRAE 62.1 OA ≈ 0.4 ACH*
Exam Room (Medical)4–6 ACH total, 2 ACH OAASHRAE 170 (total depends on edition — check the adopted one)
Patient Room4–6 ACH total, 2 ACH OAASHRAE 170 (total depends on edition / supplemental heating-cooling)
Operating Room20 ACH total, 4 ACH OAASHRAE 170
Laboratory6–10 ACH occupiedLab design practice; fume-hood exhaust often governs
Commercial Kitchen15–60 ACHRule of thumb; hood exhaust governs. IMC Table 403.3.1.1 minimum exhaust 0.7 CFM/ft²
Restroom (public)Exhaust 50 CFM per WC/urinal (70 intermittent)IMC Table 403.3.1.1
Parking Garage (enclosed)Exhaust 0.75 CFM/ft²IMC Table 403.3.1.1
WarehouseOA 10 CFM/person + 0.06 CFM/ft²ASHRAE 62.1 (≈ 0.2 ACH at 20 ft)

* ASHRAE 62.1 does not set ACH for these spaces. It sets outdoor air per person plus per square foot (Vbz = Rp·Pz + Ra·Az); the OA ACH shown is that rate at the Table 6-1 default occupant density and a 9 ft ceiling. Total-supply ACH for ordinary spaces is set by the cooling load, not by code.

Inputs, results, and method — as an Excel workbook or plain CSV.

Doing this for a whole building? See this step inside a connected AIM Works project — loads, ventilation, equipment, and Design Review in one place.

Book a Demo →
About This Calculator

This air changes per hour calculator relates supply airflow, room volume, and ventilation rate. Choose what to solve for — ACH, CFM, or room volume — enter the other two values, and the tool returns the result plus the minutes required for one complete air change. A space-type selector shows a typical target and its basis alongside your number.

Engineers use ACH to size or check ventilation against codes that specify air changes rather than CFM, and to translate between the two. The reference targets show their basis — ASHRAE 170 for healthcare air changes, IMC exhaust rates, or a rule of thumb for total supply air — so you can tell a code minimum from a design habit. ASHRAE 62.1 sets outdoor air per person and per square foot, not air changes.

Formula & Method
Air changes/hrACH = (CFM × 60) ÷ Volume (ft³)
Required airflowCFM = (ACH × Volume) ÷ 60
Room volumeVolume = (CFM × 60) ÷ ACH
Minutes per changemin/change = 60 ÷ ACH

The factor 60 converts CFM (cubic feet per minute) to cubic feet per hour so it can be divided by the room volume. Healthcare air changes follow ASHRAE 170 and exhaust rates follow IMC Table 403.3.1.1; restrooms, kitchens, and garages are specified as CFM per fixture or per square foot rather than ACH. Total-supply ACH ranges for offices, classrooms, and similar spaces are rules of thumb — ASHRAE 62.1 sets outdoor air per person and per square foot, not air changes. Confirm the governing rate against the code adopted in your jurisdiction.

Frequently Asked Questions
What does air changes per hour (ACH) mean?
ACH is the number of times the entire air volume of a room is replaced each hour. An ACH of 6 means the room's full air volume is exchanged six times per hour, or once every ten minutes. It is a convenient way to express ventilation or total supply airflow relative to room size, and it is used in many code and design guidelines for ventilation and contaminant control.
How do I convert CFM to ACH?
Multiply the airflow in CFM by 60 to get cubic feet per hour, then divide by the room volume in cubic feet: ACH = CFM times 60 divided by volume. For example, 1,000 CFM into a 10,000 cubic foot room gives 6 ACH. To go the other way, CFM = ACH times volume divided by 60. This tool solves for ACH, CFM, or volume from the other two.
What ACH does code require for my space?
It depends on the space and the governing standard. ASHRAE 62.1 does not use ACH for ordinary commercial spaces: it sets outdoor air per person plus per square foot, which works out to roughly 0.5 to 3 outdoor-air changes per hour for typical offices, conference rooms, and classrooms. ASHRAE 170 does set air changes for healthcare, such as 20 total and 4 outdoor ACH for operating rooms and 2 outdoor ACH for exam and patient rooms (the total varies by edition). The IMC sets exhaust for kitchens, toilet rooms, and parking garages per square foot or per fixture. Total-supply ACH ranges for ordinary spaces are cooling-load rules of thumb. Always confirm against the adopted code.
Is ACH the same as outdoor air ventilation?
Not necessarily. Total ACH counts all supply air moving through the space, which may be mostly recirculated air. Outdoor air changes per hour count only the fresh outdoor portion. Healthcare standards often specify both a total ACH and a minimum outdoor ACH. When comparing to a ventilation requirement, make sure you are using the right one.
Related Tools
Ventilation Calculator OA / RA % Calculator DOAS Sizing Infiltration Load Quick Load Estimator
AIM Works · launches Oct 15, 2026

Connect the calculation to the rest of the project.

AIM Works brings peak loads, ASHRAE 62.1 ventilation, equipment and plant sizing, compliance checks, Design Review, and engineering deliverables into one connected mechanical design workspace.

  • Peak loads (RTS or CLTD/CLF) and ASHRAE 62.1-2019 ventilation
  • Equipment and plant sizing against ASHRAE 90.1-2022 efficiency floors
  • Design Review that cites the check behind every finding
  • An AI co-pilot that drafts changes — you approve each one
Book a Demo →
A walkthrough first, then a 14-day free trial. No credit card.
How the calculations work →

Results are design estimates for preliminary sizing. Verify final designs against applicable codes and standards — engineering judgment and a licensed professional engineer’s review are required.