⚡ Load Inputs

From BTU/hr Values
From Airflow + Conditions
Dry heat: conduction, solar, lights, people (sensible)
Moisture: people, OA humidity, infiltration

📚 Typical SHR by Space Type

Space TypeTypical SHRLatent Load SourceLevel
Office / Commercial0.85–0.95People, ventilation OALow Latent
Retail0.80–0.90People, OA, infiltrationLow Latent
Restaurant / Kitchen0.65–0.75Cooking, high OA, steamHigh Latent
Gym / Fitness0.65–0.75Heavy occupancy sweat loadHigh Latent
Natatorium / Pool0.30–0.55Evaporation from water surfaceHigh Latent
Hospital Patient Room0.70–0.80People, OA requirementsMed Latent
Warehouse0.90–0.98Minimal occupancyLow Latent
Humid Climate (summer)0.70–0.80OA humidity, infiltrationHigh Latent
Inputs, results, and method — as an Excel workbook or plain CSV.
Book a Demo →
See this step inside a connected mechanical project — then a 14-day free trial. No credit card.

📝 About This Calculator

This sensible vs latent split calculator finds the sensible heat ratio (SHR) and the breakdown of a cooling load into dry sensible heat and moisture-removal latent heat. Enter the loads directly in BTU/hr, or enter supply airflow with room and supply dry-bulb temperatures and humidity ratios and let the tool compute each component.

SHR is the single number that tells you whether a space is mostly a cooling problem or also a humidity problem. The tool plots the split, reports total tons, and flags low-SHR cases where supplemental dehumidification — reheat, a dedicated dehumidifier, or a desiccant wheel — is usually needed.

🔢 Formula & Method

QuantityEquation
Sensible heat ratioSHR = Sensible ÷ (Sensible + Latent)
Sensible loadQ‑sens = 1.08 × CFM × ΔT (°F)
Latent loadQ‑lat = 0.68 × CFM × ΔW (gr/lb)
Total coolingTons = (Sensible + Latent) ÷ 12,000

The airside constants follow ASHRAE Fundamentals: 1.08 for sensible heat (specific heat × density × 60) and 0.68 for latent heat when the humidity-ratio difference ΔW is in grains per pound of dry air. SHR is the sensible fraction of the total; equipment SHR is typically 0.70–0.80, so a lower space SHR signals a need for supplemental dehumidification.

❓ Frequently Asked Questions

What is sensible heat ratio (SHR)?
Sensible heat ratio is the sensible cooling load divided by the total cooling load, where total is sensible plus latent. An SHR of 0.80 means 80 percent of the load is dry sensible heat and 20 percent is moisture removal. It describes the balance between cooling the air down and drying it out, which drives how a cooling coil and any dehumidification are selected.
What does a low SHR mean for equipment selection?
A low SHR, below about 0.75, means a large share of the load is latent moisture. Standard cooling equipment has an SHR near 0.70 to 0.80, so when the space SHR is even lower, the coil tends to over-cool the air before it removes enough moisture. That points to supplemental dehumidification such as hot gas reheat, a dedicated dehumidifier, or a desiccant wheel.
How is the split found from airflow and conditions?
Sensible load is 1.08 times CFM times the dry-bulb temperature difference between room and supply air. Latent load is 0.68 times CFM times the humidity-ratio difference in grains per pound between room and supply air. The 1.08 and 0.68 factors are the standard sea-level airside constants from ASHRAE Fundamentals. Adding the two gives the total, and sensible over total is the SHR.
Which spaces typically have high latent loads?
Spaces with lots of moisture or high outdoor air have low SHRs and high latent fractions: restaurants and kitchens, gyms and fitness rooms, natatoriums and pools, and any space in a humid climate with significant ventilation. Offices, retail, and warehouses are mostly sensible with SHRs from about 0.85 to 0.98. The reference table on this page lists typical values by space type.

🔗 Related Tools

Supply Air Temp Cooling Coil Calculator Quick Load Estimator Infiltration Load Humidity Ratio Lighting Heat Gain
AIM Works · launches Oct 15, 2026

Connect the calculation to the rest of the project.

AIM Works brings peak loads, ASHRAE 62.1 ventilation, equipment and plant sizing, compliance checks, Design Review, and engineering deliverables into one connected mechanical design workspace.

  • ✓  Peak loads (RTS or CLTD/CLF) and ASHRAE 62.1-2019 ventilation
  • ✓  Equipment and plant sizing against ASHRAE 90.1-2022 efficiency floors
  • ✓  Design Review that cites the check behind every finding
  • ✓  An AI co-pilot that drafts changes — you approve each one
Book a Demo →
A walkthrough first, then a 14-day free trial. No credit card.
How the calculations work →

Results are design estimates for preliminary sizing. Verify final designs against applicable codes and standards — engineering judgment and a licensed professional engineer’s review are required.