Cooling Coil Calculator

Cooling coil capacity from entering and leaving air conditions.

Air Conditions
Entering Air
Leaving Air


Coil Face (Optional — for face velocity)
Capacity Results
Total Capacity
—
tons
Total Capacity
—
BTU/h
Sensible Capacity
—
tons
Sensible Capacity
—
BTU/h
Latent Capacity
—
tons
Latent Capacity
—
BTU/h
Water Removed
—
lb/hr
Water Removed
—
GPH
Face Velocity
—
fpm
Air Density (dry-air basis)
—
lb dry air/ft³ entering
Sensible Heat Ratio (SHR) —
⚠ Leaving wet bulb is higher than leaving dry bulb — check entering/leaving conditions.
⚠ Negative latent load — leaving air is more humid than entering. Check wet bulb inputs.
Inputs, results, and method — as an Excel workbook or plain CSV.

Doing this for a whole building? See this step inside a connected AIM Works project — loads, ventilation, equipment, and Design Review in one place.

Book a Demo →
About This Calculator

This cooling coil calculator finds the total, sensible, and latent capacity a coil must deliver to move air from its entering condition to its leaving condition. Enter the entering and leaving dry-bulb and wet-bulb temperatures, the airflow in CFM, and the site elevation; the tool returns capacity in BTU/h and tons, the sensible heat ratio (SHR), the moisture removed in lb/hr and gallons per hour, and an optional face velocity from the coil dimensions.

Working from the full psychrometric state of each air stream — not just a temperature difference — lets the tool separate sensible cooling from the latent (dehumidification) load. That split drives coil row and circuit selection, chilled-water flow, and reheat strategy, so getting it right early avoids undersized coils and humidity-control problems downstream.

Formula & Method
Total: Qtotal (BTU/h) = ṁ × (hin – hout)
Sensible: Qsens (BTU/h) = ṁ × (0.240 + 0.444·Win) × (Tdb,in – Tdb,out)
Latent: Qlat = Qtotal – Qsens  ·  SHR = Qsens ÷ Qtotal
Mass flow: ṁ (lb dry air/hr) = 60 × CFM ÷ vin  ·  Water = ṁ × (Win – Wout)

Humidity ratio W comes from each dry-bulb/wet-bulb pair through the ASHRAE Handbook—Fundamentals (2021) Chapter 1 wet-bulb equation, and h = 0.240·T + W·(1061 + 0.444·T), at the standard-atmosphere barometric pressure for your elevation. The airflow is taken as actual CFM at the entering condition, so the dry-air mass flow uses the entering specific volume vin = 0.370486·(T + 459.67)·(1 + 1.607858·W)/P rather than the standard-air 0.075 lb/ft³. Standard-air shortcuts (4.5 × CFM × Δh, 1.08 × CFM × ΔT) read about 4 % higher at 80 °F entering air. Sensible heat uses the moist-air specific heat 0.240 + 0.444·W, so sensible plus latent equals the enthalpy change exactly. 12,000 BTU/h equals one ton of refrigeration, and 8.34 lb/gal converts condensate mass to gallons per hour.

Frequently Asked Questions
How is total cooling coil capacity calculated?
Total capacity is the air mass flow times the enthalpy drop across the coil: BTU/h = mass flow (lb/hr) times (h entering minus h leaving). Mass flow comes from the airflow in CFM times 60 times the actual air density, and enthalpy is found from each air stream's dry-bulb and humidity ratio. Dividing by 12,000 converts BTU/h to tons of refrigeration.
What is sensible heat ratio (SHR) and why does it matter?
SHR is the sensible capacity divided by the total capacity. It tells you how much of the coil's work goes to lowering temperature versus removing moisture. A high SHR near 0.9 means mostly dry-cooling, while a low SHR near 0.6 means heavy dehumidification. Matching coil SHR to the space load is essential for humidity control.
How does elevation affect the coil capacity?
Higher elevation lowers barometric pressure and therefore air density, so a given CFM carries less mass. Pressure also changes the humidity ratio a wet-bulb reading implies, so at altitude the same entering and leaving temperatures mean more moisture removed per pound of air. This tool corrects barometric pressure for elevation and uses the actual dry-air density at entering conditions rather than the standard 0.075 lb/ft3, which keeps capacity and moisture-removal numbers consistent at altitude.
What is a typical coil face velocity?
Cooling coils are usually designed for a face velocity of about 400 to 500 fpm. Below roughly 300 fpm the coil is oversized for the airflow; above about 500 fpm condensate carryover becomes a concern, and above roughly 550 to 600 fpm water can be blown off the fins and carried downstream unless eliminators are used. Enter both coil face dimensions and the tool flags velocities below 300 or above 500 fpm. These are typical design-practice limits, not code requirements.
Related Tools
Psychrometric Calculator Coil Leaving Air Sensible / Latent Split Chiller Size Estimator CFM / Tons / BTU Control Valve Cv Lighting Heat Gain Window Solar Heat Gain Cooling Tower
AIM Works · launches Oct 15, 2026

Connect the calculation to the rest of the project.

AIM Works brings peak loads, ASHRAE 62.1 ventilation, equipment and plant sizing, compliance checks, Design Review, and engineering deliverables into one connected mechanical design workspace.

  • Peak loads (RTS or CLTD/CLF) and ASHRAE 62.1-2019 ventilation
  • Equipment and plant sizing against ASHRAE 90.1-2022 efficiency floors
  • Design Review that cites the check behind every finding
  • An AI co-pilot that drafts changes — you approve each one
Book a Demo →
A walkthrough first, then a 14-day free trial. No credit card.
How the calculations work →

Results are design estimates for preliminary sizing. Verify final designs against applicable codes and standards — engineering judgment and a licensed professional engineer’s review are required.