❄️ Inputs

Typically 35–45°F for A/C; 20–30°F for low temp
Typically 105–130°F condensing temp

📊 Recommended ACR Copper Sizes

Suction Line
Discharge Line
Liquid Line

📚 Velocity Limits (ASHRAE / ACCA)

LineMin Velocity (FPM)Max Velocity (FPM)Purpose
Suction (horizontal)5004,000Oil return to compressor
Suction (vertical riser)1,0004,000Must entrain oil upward
Discharge (hot gas)1,0003,500Oil return; sound control
Liquid line75300Prevent flashing; low pressure drop
Run this for your whole project — free →
Start a free 14-day trial. No credit card.

About This Calculator

This refrigerant line sizer recommends ACR copper tube sizes for the suction, discharge, and liquid lines of a DX system using a velocity-based method. Enter the system tonnage, refrigerant (R-410A, R-22, R-32, or R-134a), and the suction and discharge saturation temperatures; the tool estimates mass flow, sizes each line to land within its velocity band, and reports the resulting tube size and actual velocity.

The suction and discharge (vapor) lines are sized to keep velocity high enough to return compressor oil, while the liquid line is kept slow to limit pressure drop and prevent flashing. Use the result as a preliminary check, then confirm against the equipment manufacturer's line-sizing tables.

Formula & Method

Mass flow: ṁ (lb/min) ≈ tons × 0.6 (suction)
Required area: A = ṁ ÷ (ρline × vtarget)
Actual velocity: v (fpm) = ṁ ÷ (ρline × Atube)

Mass flow is approximated at about 0.6 lb/min per ton on the suction side; ρline is the vapor density for suction and discharge and the liquid density for the liquid line. The target velocity is the midpoint of each line's recommended band, and the tool rounds up to the next standard ACR copper size. Velocity limits — oil-return minimums on vapor lines and a low maximum on the liquid line — follow ASHRAE Refrigeration and manufacturer line-sizing practice, where velocity governs oil return and pressure drop sets the saturation-temperature penalty.

Frequently Asked Questions

How does this refrigerant line sizer pick a tube size?
From the system tonnage it estimates the refrigerant mass flow, then for each line uses the appropriate vapor or liquid density to find the cross-sectional area that lands inside the target velocity band. It rounds up to the next standard ACR copper tube and reports the actual velocity for the suction, discharge, and liquid lines so you can confirm oil return and pressure drop.
What velocities are recommended for refrigerant lines?
Typical limits are about 500 to 4,000 fpm for horizontal suction, at least 1,000 fpm for vertical suction risers to entrain oil upward, 1,000 to 3,500 fpm for discharge, and a much lower 75 to 300 fpm for the liquid line. The minimums protect oil return on vapor lines, and the liquid-line maximum prevents flashing and limits pressure drop.
Why is the liquid line so much smaller than the suction line?
Liquid refrigerant is hundreds of times denser than the suction vapor, so the same mass flow occupies far less volume and needs much less pipe area to stay within its velocity band. The liquid line is also deliberately kept slow to avoid pressure drop that could flash the liquid to vapor before it reaches the metering device.
Do vertical risers need special attention?
Yes. On vertical suction risers longer than about 10 feet, velocity must stay high enough, roughly 1,000 fpm or more, to carry oil up against gravity back to the compressor. At low load a single riser may not maintain that velocity, so a double-riser arrangement is sometimes used. Confirm riser design against the manufacturer's selection tables and ASHRAE Refrigeration guidance.

Related Tools

Refrigerant Pipe Sizer Chiller Size Estimator Cooling Coil Calculator Gas Pipe Quick Estimator
Free 14-Day Trial  ·  No Credit Card

Do the full calculation in AIM Works

This calculator handles one step. AIM Works runs the complete MEP design workflow — thermal load calculations, duct & pipe networks, equipment selection, code compliance, and an AI design assistant — in one tool.

  • ✓  ASHRAE 62.1 ventilation + CLTD/CLF/RTS load methods
  • ✓  Darcy-Weisbach pipe & duct network solvers
  • ✓  ASHRAE 90.1 / IMC / NFPA advisory compliance checks
  • ✓  20 free AI design messages included in trial
Try It Free for 14 Days →
No credit card  ·  Cancel anytime
See plans & pricing →

Results are design estimates for preliminary sizing. Verify final designs against applicable codes and standards — engineering judgment and a licensed professional engineer’s review are required.