A quick-reference sheet of common HVAC rules of thumb and design constants.
| Rule | Value / Range | Notes |
|---|---|---|
| Supply duct velocity — main trunk | 1,000–2,000 FPM | Low-pressure commercial; stay toward the low end above quiet (NC 30–35) spaces |
| Supply duct velocity — branch / runout | 600–1,200 FPM; runouts ≤ 700 FPM | Slower near diffusers to limit noise |
| Return duct velocity | ≤ 1,500 FPM mains; ≤ 1,000 FPM branches | Return and transfer grilles slower still |
| Duct friction loss target | 0.08–0.10 in. w.g. per 100 ft | Equal-friction sizing, low-pressure duct, sea-level air |
| CFM/ton cooling | 350–450 CFM/ton | Comfort-cooling DX and CHW coils; lower when dehumidification governs |
| Supply air temp (cooling) | 55–60°F | Typical coil leaving air; colder where humidity control governs |
| Supply air temp (heating) | 85–120°F | Low end for overhead VAV reheat. Warm air ≥ 15°F above room from the ceiling with a ceiling return gets Ez = 0.8 in ASHRAE 62.1 Table 6-4 |
| OA fraction | Often ~10–20% in offices | An outcome, not a rule: ASHRAE 62.1 sets outdoor air in cfm (Vbz = Rp·Pz + Ra·Az, then system efficiency), not as a percent of supply. Dense spaces run far higher |
| Filter face velocity | 300–500 FPM | Most filters are rated near 500 FPM; slower means lower ΔP and longer life |
| Sensible heat factor (sea level) | 1.08 | Q = 1.08 × CFM × ΔT (BTU/hr) |
| Latent heat factor (sea level) | 0.68 | Q = 0.68 × CFM × ΔW (gr/lb) ≈ 4,840 × CFM × ΔW (lb/lb) |
| Rule | Value / Range | Notes |
|---|---|---|
| CHW ΔT (return – supply) | 10–16°F | 12°F (44/56°F) common; 14–16°F for low-flow plants |
| HHW ΔT (supply – return) | 20–40°F | 20°F traditional; 30–40°F with condensing boilers. Higher ΔT = smaller pipe and less pump energy |
| CHW GPM/ton | 24 ÷ ΔT | 2.4 GPM/ton at 10°F · 2.0 at 12°F · 1.5 at 16°F |
| Pipe friction target | 1–4 ft per 100 ft | Common design range; about 2.5 ft/100 ft for mains |
| Pipe velocity — mains | 4–8 ft/s | Noise and erosion limit; ≤ 4 ft/s in branches near occupied space |
| Pipe velocity — pump suction | ≤ 5 ft/s | Protects NPSH margin; suction pipe is often one size larger than the pump inlet |
| Hydronic factor (water) | 500 | Q = 500 × GPM × ΔT (BTU/hr); glycol mixes are lower |
| Pump efficiency (typical) | 65–80% | Centrifugal pump near its best efficiency point; larger pumps run higher |
| Rule | Value / Range | Notes |
|---|---|---|
| Comfort RH range | 30–60% | Common design practice. ASHRAE 55 sets no lower humidity limit; where humidity is controlled, its upper limit is a 0.012 lb/lb humidity ratio (about 65% RH at 75°F) |
| Cooling setpoint (occupied) | 73–78°F | 75°F common; ASHRAE 55 comfort depends on clothing, activity, humidity, and air speed |
| Cooling load — office | 300–450 ft²/ton | Modern code-built offices; the band the AIM Works app benchmarks against. Varies widely |
| Lighting load density | 0.5–1.0 W/ft² | LED office; current ASHRAE 90.1 office allowances are under 1 W/ft². Legacy fluorescent ~1.0–1.5 W/ft² |
| People load — office | 245–250 BTU/hr sensible + 155–200 latent | 400–450 BTU/hr total, seated to moderately active office work (ASHRAE Fundamentals Ch.18, Table 1) |
| Latent load fraction — humid climate | 20–35% | Of total cooling load; higher where outdoor air dominates |
| SHR — typical commercial coil | 0.70–0.80 | DX and CHW in mixed climates |
| Enthalpy — summer outdoor (SE US) | 38–42 BTU/lb | 95°F DB with 75–79°F coincident WB at sea level (enthalpy tracks wet bulb) |
| Rule | Value / Range | Notes |
|---|---|---|
| Chiller efficiency — water-cooled centrifugal | ≤ 0.610 kW/ton (< 300 tons); ≤ 0.560 kW/ton (≥ 300 tons) | ASHRAE 90.1-2022 Table 6.8.1-3 Path A full-load limits (COP ≥ 5.77 / 6.28); IPLV must also be met. New machines often select near 0.50–0.58 kW/ton |
| Chiller efficiency — air-cooled | ≥ 10.1 EER (≤ 1.19 kW/ton) | ASHRAE 90.1-2022 Table 6.8.1-3 Path A full-load minimum |
| DX system COP | ≈ 2.9–3.8 (EER ≈ 10–13) | Packaged rooftop at the AHRI full-load rating; part-load (IEER) is higher |
| Boiler efficiency (condensing) | 90–98% | Modulating; needs return water below ~130°F to condense |
| Cooling tower approach | 5–10°F | Leaving CW minus ambient WB; 7°F common (85°F at 78°F WB) |
| Fan motor sizing | BHP × 1.15–1.25 | Common selection margin, then the next standard motor size |
| VFD savings at 80% speed | Up to ~49% (ideal) | Affinity law: power ∝ speed³ (0.8³ = 0.51). Real savings are lower where a pressure setpoint or system head remains |
| Pump motor sizing | BHP = WHP ÷ pump eff; motor ≈ BHP × 1.15 | WHP = GPM × ft head × SG ÷ 3,960 |
Doing this for a whole building? See this step inside a connected AIM Works project — loads, ventilation, equipment, and Design Review in one place.
Book a Demo →This page collects the rules of thumb HVAC engineers reach for every day — duct and pipe velocity limits, chilled- and hot-water delta-T, load densities, equipment efficiencies, and the sensible and latent heat factors — into four sorted reference tables. It is a bookmark-and-go cheat sheet, not a calculator with inputs.
Rules of thumb are for fast estimating and for checking whether a detailed result is believable. They are deliberately broad, and the right value for a specific project depends on climate, building type, and code. Always confirm with a real calculation before committing a number to a drawing.
| Sensible heat (air) | Q (BTU/hr) = 1.08 × CFM × ΔT (°F), sea level |
| Latent heat (air) | Q (BTU/hr) = 0.68 × CFM × ΔW (gr/lb), sea level |
| Hydronic heat (water) | Q (BTU/hr) = 500 × GPM × ΔT (°F) |
| Cooling capacity | 1 ton = 12,000 BTU/hr = 3.517 kW |
| VFD affinity law | power ∝ speed³ → 80% speed ≈ 51% power |
The air factors 1.08 = 60 × 0.075 × 0.24 and 0.68 ≈ 60 × 0.075 × 1,076 ÷ 7,000, and the water factor 500 ≈ 60 × 8.33 × 1.0, follow standard ASHRAE Fundamentals unit relations; the air factors are sea-level values that fall with air density at altitude (about 17% lower at 5,000 ft). The affinity-law cube relationship comes from fan and pump similarity laws. Velocity, friction, and ΔT ranges are common design practice and line up with the default design criteria in the AIM Works app; efficiency limits quote ASHRAE 90.1-2022 where a standard is named. Everything else is a typical range, not a code requirement.
AIM Works brings peak loads, ASHRAE 62.1 ventilation, equipment and plant sizing, compliance checks, Design Review, and engineering deliverables into one connected mechanical design workspace.
Results are design estimates for preliminary sizing. Verify final designs against applicable codes and standards — engineering judgment and a licensed professional engineer’s review are required.